Teilenummer
					Entmilitarisierung
					Lagerfähigkeit
					UOM
					NIIN
				 
				
			 
						
				
					NSN
				
				
					Nationale Bestandsnummer:
				
				
			 
			
				
					TXT
				
				
					Beschreibung:
				
				
					Circuit Breaker				
			 
			
										
					
						MRC:
						The style designation indicating the configuration that most nearly corresponds to the appearance of the body.AAQL
					 
					
						Body Style:
					
					
						Single pole type					
				 
							
					
						MRC:
						A measurement of the longest dimension of the body,in distinction from width.ADAQ
					 
					
						Body Length:
					
					
						Between 3.480 inches and 3.520 inches 					
				 
							
					
						MRC:
						A measurement taken at right angles to the length of the body,in distinction from thickness.ADAT
					 
					
						Body Width:
					
					
						Between 0.940 inches and 0.980 inches 					
				 
							
					
						MRC:
						A measurement from the bottom to the top of the body,in distinction from depth.ADAU
					 
					
						Body Height:
					
					
						Between 3.040 inches and 3.080 inches 					
				 
							
					
						MRC:
						The element,compound,or mixture of which the case is fabricated,excluding any surface treatment.ADTV
					 
					
						Case Material:
					
					
						Plastic					
				 
							
					
						MRC:
						A designation that describes the basic electrical configuration of a switch.AEGJ
					 
					
						Switch Contact Arrangement:
					
					
						Single pole,  double throw					
				 
							
					
					
						Boss Height:
					
					
						Between 0.178 inches and 0.198 inches 					
				 
							
					
						MRC:
						The number of poles included in the item.AKPX
					 
					
						Pole Quantity:
					
					
						1					
				 
							
					
						MRC:
						Indicates the type and number of facilities by which the item is mounted.AXHR
					 
					
						Mounting Facility Type And Quantity:
					
					
						2 terminal					
				 
							
					
						MRC:
						The maximum current load that each pole is rated to carry continuously.CPLM
					 
					
						Maximum Continuous Load Current Rating Per Pole:
					
					
						10.0 amperes ac single location and 10.0 amperes dc single location					
				 
							
					
						MRC:
						Indicates the type and value of operating voltage for which each pole is designed to operate,expressed in volts.CPRF
					 
					
						Operating Voltage Type And Rating Per Pole In Volts:
					
					
						300.0 ac single location and 125.0 dc single location					
				 
							
					
						MRC:
						Indicates the type and value of the maximum short circuit current that the item will successfully interrupt,per pole,at the specified rated voltage,expressed in amperes.CPRG
					 
					
						Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps:
					
					
						5000.0 ac single location and 2500.0 dc single location					
				 
							
					
						MRC:
						Indicates the type of electrical condition that will cause the device to trip.CPRH
					 
					
						Circuit Protection Type:
					
					
						Overcurrent single location					
				 
							
					
						MRC:
						The means by which the trip mechanism is released.CPRJ
					 
					
						Trip Release Method:
					
					
						Thermal-magnetic single location					
				 
							
					
						MRC:
						Denotes the type of trip release action.CPRL
					 
					
						Trip Release Characteristic:
					
					
						Instantaneous single location and time delay single location					
				 
							
					
						MRC:
						The continuous current rating per pole at which the device must trip in a specified time,expressed in percent.CPRN
					 
					
						Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent:
					
					
						150.0 single location					
				 
							
					
						MRC:
						The means provided to reposition the mechanism so that the device is ready to function.CPRQ
					 
					
						Reset Method:
					
					
						Manual					
				 
							
					
						MRC:
						Indicates the type of mechanism provided for tripping main contacts.CPRR
					 
					
						Main Contact Tripping Mechanism Type:
					
					
						Trip free					
				 
							
					
						MRC:
						Indicates the type and number of actuators provided for manual control.CPRT
					 
					
						Manual Actuator Type And Quantity:
					
					
						1 toggle					
				 
							
					
						MRC:
						Denotes the action imparted by actuator operation.CPRW
					 
					
						Actuator Function:
					
					
						Trip-reset					
				 
							
					
						MRC:
						An indication of the designated position of the actuator.CPRX
					 
					
						Actuator Position Designation:
					
					
						At pole one					
				 
							
					
						MRC:
						The function for which the auxiliary switch is designed and the number provided.CPRZ
					 
					
						Auxiliary Switch Function And Quantity:
					
					
						1 alarm					
				 
							
					
						MRC:
						Indicates the location of the switch in relation to its designated position.CQSM
					 
					
						Switch Location And Position Designation:
					
					
						External at pole one					
				 
							
					
						MRC:
						The length of time,expressed in seconds,that an overload may exist before the device will trip at a specified continuous current.CQWN
					 
					
						Trip Delay Time In Seconds Per Rated Continuous Current:
					
					
						10.000  at 200 pct single location and 210.000  at 200 pct single location					
				 
							
					
						MRC:
						The temperature of the medium surrounding the trip release at which it can be operated continuously.CRCF
					 
					
						Trip Release Ambient Tempurature Rating:
					
					
						50.0 degrees celsius  single location					
				 
							
					
						MRC:
						Indicates the type of terminal for providing electrical connection to the switch.CRTK
					 
					
						Switch Terminal Type:
					
					
						Turret					
				 
							
					
						MRC:
						The amount of current,expressed in amperes,and the type for which the switch is rated.CSSX
					 
					
						Switch Current Rating And Type In Amps:
					
					
						5.0 ac and 5.0 dc					
				 
							
					
						MRC:
						The voltage,expressed in volts,and current type for which the switch is rated.CSWP
					 
					
						Switch Voltage Rating And Type In Volts:
					
					
						250.0 ac and 30.0 dc					
				 
							
					
						MRC:
						The cycles per second /hertz/ of the alternating current.FREQ
					 
					
						Frequency In Hertz:
					
					
						400.0 single location					
				 
							
					
						MRC:
						Indicates the type and number of terminals for providing electrical connection.TTQY
					 
					
						Terminal Type And Quantity:
					
					
						1 solder stud and 1 tab w/screw