Teilenummer
Entmilitarisierung
Lagerfähigkeit
UOM
NIIN
Teilenummer:
352250025732
NSN
Nationale Bestandsnummer:
TXT
Beschreibung:
Circuit Breaker
MRC:
The element,compound,or mixture of which the case is fabricated,excluding any surface treatment.ADTV
Case Material:
Plastic
MRC:
A designation that describes the basic electrical configuration of a switch.AEGJ
Switch Contact Arrangement:
Single pole, double throw
MRC:
The number of poles included in the item.AKPX
Pole Quantity:
2
MRC:
The maximum current load that each pole is rated to carry continuously.CPLM
Maximum Continuous Load Current Rating Per Pole:
500.0 milliamperes dc all locations
MRC:
Indicates the type and value of operating voltage for which each pole is designed to operate,expressed in volts.CPRF
Operating Voltage Type And Rating Per Pole In Volts:
130.0 dc all locations
MRC:
Denotes the type of trip release action.CPRL
Trip Release Characteristic:
Time delay all locations
MRC:
The continuous current rating per pole at which the device must trip in a specified time,expressed in percent.CPRN
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent:
125.0 all locations
MRC:
The ultimate time per pole in which the device must trip,expressed in seconds.CPRP
Ultimate Trip Time Per Pole In Seconds:
0.500 all locations and 6.500 all locations
MRC:
Indicates the type and number of actuators provided for manual control.CPRT
Manual Actuator Type And Quantity:
1 toggle
MRC:
The function for which the auxiliary switch is designed and the number provided.CPRZ
Auxiliary Switch Function And Quantity:
1 alarm
MRC:
Indicates the location of the switch in relation to its designated position.CQSM
Switch Location And Position Designation:
Internal at pole one
MRC:
The length of time,expressed in seconds,that an overload may exist before the device will trip at a specified continuous current.CQWN
Trip Delay Time In Seconds Per Rated Continuous Current:
0.130 at 200 pct all locations and 1.200 at 200 pct all locations and 0.031 at 400 pct all locations and 0.220 at 400 pct all locations and 0.011 at 600 pct all locations and 0.110 at 600 pct all locations
MRC:
Indicates the type and number of terminals for providing electrical connection.TTQY
Terminal Type And Quantity:
4 screw