Informationen zum Teil
Programming to automatically increase output up to 30 percent when input falls between 81 vac to 106 vac; automatically decreases output up to 15 percent when input is between 127 vac and 143 vac; overload protection on battery-internal current limiting and on line circuit breaker; modem/10 base-t/100 base-tx network cable port using single line (2 wire, rj11) or network (utp, rj45) compatible jacks; battery is user replaceable, hot swappable, sealed, and maintenance free; 14 day auto self test of all internal components; leds indicate when on line, on battery, ups overload, and replace battery; alarms for on battery, low battery, and ups overload; data saving unattended shutdown, advanced power management and diagnostic software included; db 9 serial interface port; output voltage on battery is stepped approximation to sine wave output at 115 vac plus or minus 8 percent
NSN
Nationale Bestandsnummer:
TXT
Beschreibung:
Power Supply
MRC:
The dimension measured along the longitudinal axis with terminated points at the extreme ends of the item.ABHP
Overall Length:
14.500 inches
MRC:
The distance measured in a straight line from the bottom to the top of an item.ABKW
Overall Height:
6.600 inches
MRC:
An overall measurement taken at right angles to the length of an item,in distinction from thickness.ABMK
Overall Width:
4.700 inches
MRC:
The maximum altitude at which the item is rated to function.AKAE
Maximum Operating Altitude Rating:
10000.0 feet
MRC:
The relationship of the electrical power source to the item.AKWC
Electrical Power Source Relationship:
Operating
MRC:
The installation for which the item is designed.AMQY
Installation Design:
Cabinet with complete hardware
MRC:
The number of input alternating current phase(s).ANPM
Input Phase:
Single single operating power rqmt
MRC:
The input value/s/,or range of values,for which the item is rated.APNX
Input Voltage Rating:
120.0 ac pounds per hour wet single operating power rqmt
MRC:
The output value/s/,or range of values,for which the item is rated.APPA
Output Voltage Rating:
115.0 ac volts single power output
MRC:
The number of complete cyclic changes,per unit of time,for which the input is rated.APTQ
Input Frequency Rating:
47.5 hertz single operating power rqmt and 63.0 hertz single operating power rqmt
MRC:
The number of complete cyclic changes,per unit of time,for which the output is rated.APTS
Output Frequency Rating:
49.9 hertz single power output and 60.1 hertz single power output
MRC:
The ambient temperature range at which the item is designed to operate.AYNH
Operating Ambient Tempurature Range:
+32.0/+104.0 degrees fahrenheit
MRC:
The number of output control(s) provided.BGHX
Output Control Quantity:
2 single power output
MRC:
Indicates the type of output control provided.BGHY
Output Control Type:
Voltage range single power output
MRC:
The rated output power that an item can safely consume or provide,measured in watts.BGQR
Output Wattage Rating:
410.0 watts single power output
MRC:
Those features,not otherwise specified,which may be required for proper functioning of the item.CBBL
Features Provided:
Battery charger and circuit breaker and current regulator circuit and emi filter and indicator light and over voltage protector and programmable
MRC:
The output current rating at which the item is designed to operate.CWGH
Output Current Rating:
650.0 ac volt-ampere single power output
MRC:
The number of output alternating current phases.CWGN
Output Phase:
Single single power output
MRC:
An indication of whether current or voltage or both are controlled,stabilized,or limited to obtain the required output power characteristics.CWGW
Power Supply Output Current/voltage Characteristics:
Limiting voltage single power output
MRC:
The number of electrical output connections on the item.CWHF
Output Connection Quantity:
6 single power output
MRC:
Indicates the type of electrical output connection.CWHJ
Output Connection Type:
Receptacle, electrical single power output
MRC:
Indicates the type of electrical input connection.CWHQ
Input Connection Type:
Connector, plug single operating power rqmt
MRC:
The number of electrical input connections on the item.CWHT
Input Connection Quantity:
2 single operating power rqmt
MRC:
An indication of whether or not the battery is rechargeable and the type of battery.CWHY
Battery Feature And Type:
Rechargeable lead acid cell
MRC:
The time required to charge a battery(ies) to its rated capacity after a period of discharge.CWWB
Battery Recovery Time:
180.0
MRC:
The program(s) for which the power supply is design compatible.CWWJ
Program Compatibility:
Apple, ibm compatible or unix personal computers
MRC:
The time required for a battery power supply to switch from standby mode to full rated output power.CXMN
Battery Switching Time:
Two milliseconds
MRC:
The emergency operating time a battery power supply can deliver full rated output voltage/current before the output drops below a specified value.CXMX
Battery Power Supply Emergency Operating Time:
6.0
MRC:
The number of power supplies controlled by a programmable power supply.CXNJ
Power Supplies Programmed Per System:
2