Teilenummer
					Entmilitarisierung
					Lagerfähigkeit
					UOM
					NIIN
				 
				
					
						Teilenummer:
						cm30100s1ebstd					
 
					
					
					
					
				 
			 
							
					
						Informationen zum Teil
						Universal process controller,  1/4 din
					 
				 
						
				
					NSN
				
				
					Nationale Bestandsnummer:
				
				
			 
			
				
					TXT
				
				
					Beschreibung:
				
				
					Controller Electrical				
			 
			
										
					
						MRC:
						The dimension measured along the longitudinal axis with terminated points at the extreme ends of the item.ABHP
					 
					
						Overall Length:
					
					
						5.500 inches 					
				 
							
					
						MRC:
						The distance measured in a straight line from the bottom to the top of an item.ABKW
					 
					
						Overall Height:
					
					
						3.800 inches 					
				 
							
					
						MRC:
						An overall measurement taken at right angles to the length of an item,in distinction from thickness.ABMK
					 
					
						Overall Width:
					
					
						3.800 inches 					
				 
							
					
						MRC:
						The means by which the item is actuated.AFLW
					 
					
						Actuation Method:
					
					
						Manual					
				 
							
					
						MRC:
						Indicates the performance capability of the item or component.AGLD
					 
					
						Performance Type:
					
					
						Manual					
				 
							
					
						MRC:
						The working period under which the item was designed to operate.AKPS
					 
					
						Duty Cycle:
					
					
						Continuous					
				 
							
					
						MRC:
						The pattern or arrangement that describes the mounting configuration of the item.ALGC
					 
					
						Mounting Configuration:
					
					
						Standard					
				 
							
					
						MRC:
						An indication of the characteristic of the operating voltage.ANCN
					 
					
						Operating Voltage Characteristic:
					
					
						Full					
				 
							
					
						MRC:
						The voltage required to actuate the item.ANDE
					 
					
						Actuator Voltage:
					
					
						10.0 dc and 36.0 dc					
				 
							
					
						MRC:
						The temperature of the medium surrounding an item at which it can be operated.ANDX
					 
					
						Ambient Temp:
					
					
						32.0 degrees fahrenheit and 131.0 degrees fahrenheit					
				 
							
					
						MRC:
						An indication of whether or not the item is designed in conformance with the national electrical manufacturers association (nema) standards.ANQC
					 
					
						National Electrical Manufacturers Association Standards Design:
					
					
						Not designed per nema std					
				 
							
					
						MRC:
						Indicates the type of control.AQZF
					 
					
						Control Type:
					
					
						Local					
				 
							
					
						MRC:
						Those unusual or unique characteristics or qualities of an item not covered in the other requirements and which are determined to be essential for identification.FEAT
					 
					
						Special Features:
					
					
						2 analog inputs,  1 analog output,  and 2 relays; power supply is 10.0 - 36.0 vdc